Description of Standard Mobile Rental Theatre Module 14055 BS
Theatre centre 14055 BS with associated rooms, consists of:
- Anaesthetic room
- Scrub up
- Theatre
- Plantroom
External finishes
- Mineral wool external insulation, covered with, rendered finish, colour white
- Eaves from Aluminium, approx. 200mm height
Carcass, structure
- Floor construction made from rust protected steel profiles, insulation with mineral wool, OSB - plate and vacuum concrete Fire resistance 60min, imposed floor load 350 kg/m2. External walls made from rust protected steel profiles, insulation with mineral wool and Fermacell boards Fire resistance 6Omin
- Roof construction made from rust protected steel profiles, insulation with mineral wool and Fermacell boards Fire resistance 6Omin, Roof load 125 kg/m2
- "0"-degree roof, sealed with a roof membrane, internal rain water drains
- Internal walls dry lining systems, boarding with Fermacell boards
Wall surfaces
- PVC-wall surface in the theatre, anaesthetic and scrub up room Eggshell white in the plantroom
- S/S edge protection, where necessary
Flooring
- PVC with welded joints, coved skirtings in the theatre, anaesthetic and scrub up room
- PVC with welded joints, standard skirting
Ceilings
- Suspended ceiling with metal tiles 62,5 x 62,5 in the theatre, anaesthetic and scrub up room
- SPlantroom solid ceiling painted white
Internal doorsets
Door between the scrub up and the theatre:
- Automatic doorset single swing with integrated window, electrical driven, controlled via switch, laminated surface, S/S frame
- Door between the anaesthetic room and the theatre:
- Manually operated sliding door with integrated window, laminated surface, S/S frame
- Door between the scrub up and the corridor:
- Manually operated swinging door, laminated surface, S/S frame
- Door between the anaesthetic room and the corridor:
- Manually operated swinging door, laminated surface, S/S frame
External door
Door to the plantroom:
- Insulated steel doorset, painted light grey
Electrical installation according to BS
- Distributions
- IPS and UPS
- Bender theatre control panel
- Wiring and cabling
- Clean room lighting, IP 65
- Switches, socket outlets for telephone and data only conduit system (installation by others)
- Emergency lighting
- Bonding
Ventilation and cooling according to BS
Hygienic ventilation and air conditioning system following the HTM 2025. We assumed the following technical basic data's:
- Fresh air summer: 28^; 50% rel. humidity
- Fresh air winter: -7 °C; 90 % rel. humidity
- Room temperature: 19 - 23 °C
- Rel. humidity: 40% - 60%
- Room class: I
- Supply air volume flow: approx. 4.500 m3/h
- Total air volume canopy: approx. 12.500 m3/h
Max. cooling load per theatre: 3,5 kW The system consists of the following components:
- 1 no compact ventilation unit with integrated cooling and heating coils, filter class F7 and F9, heat recovery, humidifier, fans, condenser and control unit PC-3 Type: WEISS, Mediclean 75.3 DXL
- 1 no clean air canopy for 12.500 m3/h, size 2,9m x 2,9m x 0,45m, Filter class H14 Type: WEISS, FFA.3 29/29
- 2no circulating air modules, pre filter F7, air volume 4.000 m3/h
- Duct work with insulation
- Other components like weather protection grids, silencer, fire damper, air flow controller, pressure stabilisizer, electric air heater
Sanitary installation
- The installation will be in the walls
- Supply and drain water system, where water is required
Heating
- Via ventilation system, static radiators where necessary
- Connection of the heating coils in the ventilation unit
Medical gases
- All installation with copper pipes according to British standard
- In the anaesthetic room wall outlets for O2, compressed air 5 bar, compressed air 10 bar (Air motor), Vacuum, N20 as well as the control panels for the medical gases
- In the theatre in the pendants
- Connecting point medical gases in the floor or the suspended ceiling of the anaesthetic room
The rooms are equipped with the following parts
Anaesthetic room:
- Cupboard with working plate and integrated wash basin integrated drugs cupboard and refrigerator
- 2no control panels for medical gases
- Anaesthetic working area equipped with: 2no rails for medical utilities
- 1no subconstuction for an anaesthetic machine Drager wall mounted gas outlets 2 No O2
- 2 No compressed air 5 bar 2 No Vacuum 2 No N20
- 1 No suction for anaesthetic gas
- Conduit system with 2no boxes for the telephone or data wiring (wiring and boxes are done by others)
Theatre:
- Canopy 2,9m x 2,9m
- Theatre light with satellite, DRAGER, Type SOLA 700/500
- Theatre control panel with X-Ray viewer, clock, alarms a.s.o.; type Bender
- 1 no pendant Anaesthetic, DRAGER, Type Movita lift express max. loading: 80kg equipped with: 2no O2
- 2 No compressed air 5 bar
- 2 No N20
- 2 No Vacuum
- 1 No suction for anaesthetic gas
- 4 No safety socket outlets
- 2 No UPS socket outlets
- 6 No earth connections
- 2 no empty boxes (spare boxes for instance for IT connections)
- 1 no pendant Chirurgie, DRAGER, Type Movita lift express max. loading: 80kg equipped with:
- 2 no compressed air 5 bar 2 no compressed air 10 bar (Air motor) 2 no Vacuum 4 no safety socket outlets 2 no UPS socket outlets 6 no earth connections 2 no empty boxes (spare boxes for instance for IT connections)
- 4 no socket outlets in the wall (safety circuit)
- 4 no socket outlets in the wall (UPS)
- 8 no earth connections in the wall
- 2no rails for medical utilities
- Bender theatre control panel
- Conduit system with 2no boxes for the telephone or data wiring (wiring and boxes are done by others)
Scrub up:
- Wash basin from S/S or Corian with 2no washing places
- 2 no taps
- Thermostat for the adjustment of the water
Plant room:
- Electrical distributions connecting point of the external cables
- Electrical frost control unit
- Ventilation units
- Connecting point for heating energy
- Connecting point for water
tel 01623 651211 fax 01623 651133
email info@medi-cell.biz